VEGA VEGATROL 20 Ex User Manual

Page 8

Advertising
background image

VEGATROL 20 Ex

8

Electrical protective measures

Protection

unassembled

IP 00

installed in

Carrier Type 596 Ex with Ex-module
front completely equipped ......................... IP30
Upper and lower side ................................ IP20
Wiring side rear ......................................... IP00

installed in

Housing Type 589 - 10 Ex ......................... IP30
(in both cases observe the respective TIB)

Protection class

II (in housing 589)

Overvoltage category

II

Mechanical data

Series

Module unit for carrier type 596 Ex or
housing 589 - 10 Ex

Dimensions unassembled

W = 50,8 mm (10 TE), H = 128,4 mm, D = 162 mm

Dimensions in plastic housing 589

W = 62,5 mm, H = 136 mm, D = 222 mm

Weight

approx. 400 g

VEGATOR 526 W Ex must only be connected to instruments in which no higher voltages than AC 250 V (50 Hz) occur.

Potential stages and galvanic separation

2 Technical Information

2.4.2 Sensor VEGASWING Ex with oscillator E86 Ex (overfill protection)

Supply and signal circuit

Power supply

12 … 18,9 V DC
(from signal conditioning instrument VEGATOR 526 W Ex)

Data transmission

analog, 4 … 20 mA

Flame proofing

EEx ia IIC, T4

Internal effective capacitance

C

int

unimportant

Internal effective inductance

L

int

unimportant

Power consumption

Tuning fork uncovered

ca. 7 mA

Tuning fork covered

10 … 20 mA

Fault signal

approx. 25 mA

Reference value

approx. 15 mA

Connection line

2-wire

Ambient conditions

Permissible operating temperature

-30

°

C … +70

°

C

Storage and transport temperature

-40

°

C … +80

°

C

Operating pressure

max. 25 bar
however observe max. permissible pressure of the flange

Electrical connections

Terminals in plastic housing

for connection of max. 1,5 mm

2

Cable entry

Pg 13,5

Electrical protective measures

Protection class

II

P1

P3

P4

P5

P2

Meas. data input

Power sup. unit

P1 … P5
Potential stages

Microcomputer control and output

Relay contacts

Relay contacts

Sensor
Ex-area

Fail safe relay

Level relay

Voltage supply