6 Setup with the integrated display and adjustment unit

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

Digital HART transmission

For transmission via HART, VEGAMET 624 must be informed which

sensor value should be used for further processing. Depending on

the sensor type, this can be distance, pressure or temperature. With

all HART sensors, the unchanged initial value of the sensor is always

transmitted to VEGAMET 624. Thus, adjustment must always be car-

ried out on VEGAMET 624, never on the sensor. Different parameters

and measuring units are available.
When HART sensors from other manufacturers are connected, the

options PV (Primary Value) and SV (Secondary Value) are available.

The prerequisite for this is the support of the HART commands 0, 1,

3, and 15. This information and which measured values are transmit-

ted can be found in the operating instructions manual of the respec-

tive sensor manufacturer.

The measured variable defines the applicaton of the measurement

loop, the following settings are available depending on the connected

sensor:

Level

Process pressure

Universal (for sensors of other manufacturers)

Through the adjustment the input value of the connected sensor is

converted into a percentage value. This conversion step allows any

input value range to be depicted in a relative range (0 % up to 100 %).
Before carrying out the adjustment, the requested adjustment unit can

be selected. With input selection "Analogue", the adjustment unit is al-

ways "mA". If the HART input is activated, the available unit depends

on the sensor type. With radar, ultrasonic and guided microwave this

is always the distance in metres or feet "m(d)" or "ft(d)", and with pres-

sure transmitters it is e.g. "bar" or "psi".

The following illustrations and examples relate to the min./max. ad-

justment of a radar sensor with HART communication.

Meas. loop - Parameter

Meas. loop - Adjustment