VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART two-wire User Manual
Page 43
![background image](/manuals/262036/43/background.png)
l
S
caling
l
C
urrent output
l
U
nit of measurement
l
L
anguage
T
he following safety-relevant data are not read out or written:
l
HART
mode
l
PIN
l
SIL
C
opy sensor data
C
opy sensor data?
Basic adjustment
I
f the "Reset" is carried out, the sensor resets the values of the
following functions to the reset values (see chart):
1)
Function
Reset value
M
ax. adjustment
0
m(d)
M
in. adjustment
15
m(d) (VEGAPULS 67)
70
m(d) (VEGAPULS 68)
M
edium
B
ulk solid
V
essel form
not known
D
amping
0
s
L
inearisation
linear
S
ensor-TAG
S
ensor
D
isplayed value
D
istance
E
xtended settings
N
one
C
urrent output - characteristics
4 … 20
mA
C
urrent output - max. current
20
mA
C
urrent output - min. current
4
mA
C
urrent output - failure
<
3.6
mA
U
nit of measurement
m(d)
T
he values of the following functions are not reset to the reset values
(
see chart) with "Reset":
Function
Reset value
L
ighting
no reset
L
anguage
no reset
SIL
no reset
HART
mode
no reset
1)
S
ensor-specific basic adjustment.
Reset
VEGAPULS
68 • 4 … 20
mA/HART two-wire
43