VEGA VEGAMET 625 User Manual

Page 19

Advertising
background image

19

6 Setup with the integrated display and adjustment unit

VEGAMET 625 • Double channel HART

28970-EN-130701

Select the menu item "Device settings" with [->] and confirm with

[OK].

Under the menu item "Device settings", you can select the requested

application. For all level, gauge and differential measurements, the

application "Standard" is correct.
If an interface measurement should be carried out with a VEGAFLEX

67, you have to choose the menu item "Interface measurement" as

application. After the configuration of the inputs, the exact dielectric

figure for the upper medium must be entered. For further information

see chapter "Application examples".

Select the requested application with [->] and save your setting

with [OK]. Finally change to the menu item "Input" with [->].

Because VEGAMET 625 has two inputs, the measurement loops

must be assigned to the inputs. After the addresses of the HART sen-

sors are assigned, a list of the existing sensors can be prepared and

displayed via "Sensor selection - Sensor search". Now you can assign

the requested sensor to each measurement loop.

For transmission, VEGAMET 625 must be informed which "Sensor

value" should be used for further processing. Depending on the sen-

sor type this can be distance, pressure, interface or temperature. You

will find further information under the menu item "Meas. loop - Input".

Allocate the requested inputs to the appropriate measurement

loops, select the suitable sensor value and save your settings with

[OK]. After the first setup, you can modify the inputs also under

"Meas. loop - Input".

You can assign an unambiguous name to VEGAMET 625 via the

Device-TAG. This function is recommended when several instruments

are implemented and a good documentation of larger systems is

required.

Enter the requested values via the appropriate keys and save

your settings with [OK].

For instruments with integrated Ethernet interface, the automatic

addressing via DHCP is preset, i.e. the IP address must be assigned

by a DHCP server. Generally the instrument is contacted via the Host

Device settings - Applica-

tion

Device settings - Input

Device settings - Device-

TAG

Device settings - Host

Name/IP addr.

Advertising