8 Application examples

VEGAMET 625 • Double channel HART

28970-EN-130701

Depending on the type and version, each flume generates a different

backwater. The data of the following flumes are available in the instru-

ment:

•

Palmer-Bowlus-Flume

•

Venturi flume, trapezoidal weir, rectangular weir

•

Rectangular weir, V-Notch

Setup

The configuration of the flow measurement loop requires PACTware

with the suitable DTMs. The example refers to a flow measurement

with a radar sensor. The following setup steps must be carried out:

•

Selection of the parameter "Flow"

•

Carrying out adjustment

•

Select flume (linearization)

•

Set scaling

•

Parameter adjustment of pulse outputs

Select in the DTM window "Parameter" the option "Flow" with the

requested unit of measurement.

Min. adjustment: Enter the suitable value for 0 %, i.e. the distance

from the sensor to the medium as long as there is no flow. These are

in the following example 1.40 m.
Max. adjustment: Enter the suitable value for 100 %, i.e. the distance

from the sensor to the medium, with the max. flow volume. This is

0.80 m in the following example.

100%

0,80m (d)

=

400m

3

/h

=

0%

1,40m (d)

=

0m

3

/h

=

Fig. 16: Adjustment of flow measurement with V-notch

Select in the DTM window "Linearization" the option "Flow" and then

the used flume (in the above example V-notch).

Select in the DTM window "Scaling" under "Parameter" the option

"Flow". Finally the allocation of a value must be carried out, i.e. the

flow volume is assigned to the 0 and 100 % value. As the last step,

select the requested meas. unit. For above example: 0 % = 0 and

100 % = 400, meas. unit m³/h.

Flume

Parameter - Flow

Adjustment

Linearization curve

Scaling