VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual
Page 38
l
Medium
l
Standpipe inner diameter
2)
l
Vessel form
l
Damping
l
Linearisation curve
l
Sensor-TAG
l
Displayed value
l
Scaling unit (Out-Scale unit)
l
Positions after the decimal point (scaled)
l
Scaling PA/Out-Scale 4 values
l
Unit of measurement
l
Language
The following safety-relevant data are not read out or written:
l
Sensor address
l
PIN
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following functions to the reset values (see chart):
3)
Function
Reset value
Sensor address
126
Max. adjustment
0 m(d)
Min. adjustment
Meas. range end in m(d)
4)
Medium
Bulk solid
Vessel form
not known
Damping
0 s
Linearisation
linear
Channel
PV lin. %
Sensor-TAG
Sensor
Displayed value
PA-Out
Extended settings
None
Additional PA value
Secondary Value 1 %
Out-Scale-Unit
%
PV-Out-Scale
0.00 lin-% = 0.0 %
100.0 lin-% = 100 %
Unit of measurement
m(d)
2)
With standpipe versions.
3)
Sensor-specific basic adjustment.
4)
Depending on the sensor type, see chapter "Technical data".
Reset
38
VEGAPULS
67 • Profibus PA
6 Set up with the indicating and adjustment module PLICSCOM