6 Set up with the display and adjustment module
SOLITRAC 31 • 4 … 20 mA/HART - four-wire
40090-EN-131119
Setup
In this menu item you can assign an unambiguous name to the sen-
sor or the measurement loop.
This parameter is described in the operating instructions manual
"Display and adjustment module".
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-
plication. You can choose between the following applications: "Level",
"Point level" or "Summation Slave".
In this menu item you can activate the function of the current output.
When the output is activated, the instrument remains in its function as
a Slave, but the 4 … 20 mA output of the SOLITRAC 31 can be also
used als single instrument.
When the output is active, the instrument has the complete function-
ality of a level measuring instrument. In this case, continue reading
under "Parameter adjustment/Level measurement".
With this menu item you safeguard the sensor parameters against
unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual
"Display and adjustment module".
Additional adjustments
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, SIL and HART mode.
The following reset functions are available:
Basic settings: Resetting of the parameter adjustments to default
values at the time of shipment. Order-specific settings are deleted.
Default settings: Resetting of the parameter adjustment like under
"Basic settings". In addition, special parameters are reset to default
values. Order-specific settings are deleted.
Peak values of measured value: Resetting of the parameter adjust-
ments in the menu item "Setup" to the default values of the respective
Setup - Measurement
loop name
Setup - Application
Setup/Outputs
Lock setup - adjustment
Additional adjustments
- Reset