6 Set up with the display and adjustment module
SOLITRAC 31 • 4 … 20 mA/HART - four-wire
40090-EN-131119
instrument. Order-specific settings remain but are not taken over into
the current parameters.
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "Level". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Setup
Measurement loop name
Sensor
Isotope
Cs-137
Application
Summation Slave
Outputs
Deactivated
Adjustment
0 %, 100 %
Linearization
0 ct/s ≙ 100 %
90000 ct/s ≙ 0 %
Background radiation
0 ct/s
Unit of the process value
%
Temperature unit
°C
Damping
60 s (manually)
Real value correction
0
Current output
Deactivated
Current output mode
4 … 20 mA, < 3.6 mA
Current output Min./Max.
Min. current 3.8 mA, max. current 20.5 mA
Reference value - Relay
None
Mode
Overfill protection
Upper switching point -
Process value
0 %
Lower switching point -
Process value
0 %
Upper switching point -
Temperature
50 °C
Upper switching point -
Temperature
25 °C
Block adjustment
Released
Address - Summation
Slave
free
Display
Language
Selected language
Displayed value
Pulse rate
Display unit
ct/s