6 Set up with the display and adjustment module PLICSCOM

VEGABAR 54 • Foundation Fieldbus

36732-EN-130321

Language

The following safety-relevant data are not read out or written:

PIN

Application

Copy sensor data

Copy sensor data?

The reset function resets all parameters adjusted by the user to the

delivery status and the peak values to the actual values.

Reset

Select reset?

Reset
Basic adjustment
Peak value, measured value
Peak value, temperature

Basic adjustment

The "Reset" "Basic adjustment" resets the values of the following

menu items:

Menu section

Function

Reset value

Basic settings

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Damping

0 s

Linearization

Linear

Sensor-TAG

Sensor

Display

Displayed value

AI-Out

The values of the following menu items are not reset with "Reset:

Menu section

Function

Reset value

Basic settings

Unit of measurement

No reset

Temperature unit

No reset

Position correction

No reset

Display

Backlight

No reset

Service

Language

No reset

Application

No reset

Reset