4 Mounting

VEGAPULS 66 • Modbus and Levelmaster protocol

41366-EN-121011

0 %

100 %

1

2

5

4

3

6

Fig. 16: Configuration bypass
1 Radar sensor

2 Marking of the polarisation direction

3 Instrument flange

4 Distance sensor reference plane to upper tube connection

5 Distance of the tube connections

6 Ball valve with complete opening

Instructions for orientation:

•

Note marking of the polarisation plane on the sensor

•

With threaded fitting, the marking is on the hexagon, with flange

connection between the two flange holes

•

The pipe connections to the vessel must be in one plane with this

marking

Instructions for the measurement:

•

The 100 % point must not be above the upper tube connection to

the vessel

•

The 0 % point must not be below the lower tube connection to the

vessel

•

Min. distance sensor reference plane to the upper edge upper

tube connection > 300 mm

•

The tube diameter must be at least DN 40 or 1½" with antenna

size 40 mm (1½")