4 Mounting
VEGASWING 66 • - Relay
44950-EN-130805
The max. permissible pressure is specified in chapter "Technical
data"	or	on	the	type	label	of	the	sensor.
Note:
Seal	for	instruments	with	process	fitting	thread
The thread and the seal form on the mounting boss correspond to 
DIN 3852, part 1, screwed plug Form B (sealing via metallic sealing
edge). In this case, no seal is required.
Instruments for high temperatures have a temperature adapter be-
tween process fitting and electronics housing. This is used for thermal
decoupling of the electronics from high process temperatures.
Information:
The temperature adapter may be embedded in the vessel insulation
only up to max. 50 mm (1.97 in). Only then is a reliable temperature
decoupling guaranteed.
1
2
Fig. 8: Mounting the instrument on insulated vessels.
1 Temperature isolation - max. 50 mm (1.97 in)
2 Ambient temperature on the housing
If VEGASWING 66 is mounted in the filling stream, unwanted false
measurement signals can be generated. For this reason, mount VE-
GASWING 66 at a position in the vessel where no disturbances, e.g.
from	filling	openings,	agitators,	etc.,	can	occur.
This applies particularly to instrument types with long extension tube.
Mounting in the vessel
insulation
Inflowing medium