37

6 Set up with the display and adjustment module

MINITRAC 31 • Foundation Fieldbus

41782-EN-131119

In this menu item you can select the units of the process value and

the temperature.

In this menu item you can enter the measuring range (min. and max.

process value) of the sensor.
These settings influence the current output of the sensor.

Enter in the menu window "Max. process value" the max. density

value, for example in "g/cm

3

". This corresponds to an output current

of 20 mA.

Enter in the menu window "Min. process value" the min. density value,

for example in "g/cm

3

". This corresponds to an output current of 4 mA.

In this menu item you can enter the inside diameter of the tube or the

radiated length (L).
This setting influences the accuracy of the sensor.

First of all, select the unit of the inside diameter.

Enter in the menu window "Inside diameter" the inside diamter of the

tube, for example in "cm".

Setup - Units

Setup - Adjustment

Setup - Inside diameter