VEGA MINITRAC 31 Foundation Fieldbus User Manual

Page 42

Advertising
background image

42

6 Set up with the display and adjustment module

MINITRAC 31 • Foundation Fieldbus

41782-EN-131119

The implementation of a real value corretion is only necessary if the

requirements of the measurement loop have changed, for example

with abrasion in a tube.
If you know the density of a certain medium, you can enter the deter-

mined real density in this menu item to correct the measured value.

The function shifts the linearization curve to this determined point.
The measurement can thus be adapted exactly to the conditions in

the tube.

In this menu item you can activate the relay output and determine its

function as well as the switching points.
When the output of the process values is set, you can choose be-

tween overfill and dry run protection.
The relay outputs of the sensor react accordingly.
The following reference values can be selected:

None - Relay operates as fail safe relay

Electronics temperature

Process value

"No" reference value means that the relay output operates as fail safe

relay.

Push the [->] button, to reach the relay settings.
Example for the adjustment of the process value
First of all select the requested mode (overfill or dry run protection).

Caution:

Independent of the selected reference value, the relay will deenergize

in case of failure.

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual

"Display and adjustment module".

Setup - Real value correc-

tion (manually)

Setup - Relay

Lock setup - adjustment

Advertising