VEGA VEGAFLEX 81 Modbus and Levelmaster protocol User Manual
Page 76

76
11 Supplement
VEGAFLEX 81 • Modbus and Levelmaster protocol
41828-EN-130314
L
0
-15 mm
(-0.591")
2 mm
(0.079")
-2 mm
(-0.079")
15 mm
(0.591")
0,3 m
(11.811")
0,15 m
(5.906")
0,08 m
(3.15")
0,05 m
(1.969")
1
1
Fig. 41: Deviation VEGAFLEX 81 in cable version ø 2 mm (0.079 in), in oil
1 Dead band - no measurement possible in this area
L Probe length
0
-15 mm
(-0.591")
2 mm
(0.079")
-2 mm
(-0.079")
15 mm
(0.591")
0,3 m
(11.811")
0,15 m
(5.906")
0,15 m
(5.906")
20 mm
(0.787")
0,05 m
(1.969")
1
1
L
Fig. 42: Deviation VEGAFLEX 81 in cable version ø 4 mm (0.157 in), in oil
1 Dead band - no measurement possible in this area
L Probe length
Repeatability
≤ ±1 mm
Variables influencing measurement accuracy
Temperature drift - Digital output
±3 mm/10 K relating to the max. measuring range or
max. 10 mm (0.394 in)
Additional deviation through electromag-
netic interference acc. to EN 61326
< ±10 mm (< ±0.394 in)