Abb total flow, Wiring plan, Parameter – VEGA VEGAFLEX 81 Modbus and Levelmaster protocol User Manual
Page 92: 11 supplement
Advertising
92
11 Supplement
VEGAFLEX 81 • Modbus and Levelmaster protocol
41828-EN-130314
ABB Total Flow
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
2
13
45
2o
ff
on
( )
(
)
(-)
(-)
8
1
2
6
7
Bus +
Bus -
GND
VBAT
Fig. 47: Connection of VEGAFLEX 81 to RTU ABB Total Flow
1 VEGAFLEX 81
2 RTU ABB Total Flow
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1
The basic number of the input registers is always added to the input register address of VEGAFLEX
81.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.
Advertising