PROFIBUS P

A

63

Field-bus components for the area EEx (ia)

Technical data for pages 64-67

Temperature range

Operating temperature

from -40 to 60°C

Type of protection

IP 66

Material of housing

high-quality aluminium alloy (AL - Si 12)

Surface

stove-enamelled RAL 5015

PROFIBUS-PA - Connection

tension clamp connection 0.5 - 1.5 mm2

Cable bushing

Cable gland M16

Clamping area

5.5 - 9.5 mm

Measuring instrument connector M12 x 1 4-pole

contacts brass, surface CUZnAu

Installation advice

Torques

M16 cable gland on housing

6.25 Nm

Coupling ring M16 cable gland

4.5 Nm

Housing lid

1.8 - 2.0 Nm

Adapter / stub cable

hand-tight

External earthing cable

1.8 - 2.0 Nm

Fieldbus cable
Shielding

8

50 … 70

6

Shield is connected to the enclosure via the EMC cable glands.
Thread the cable gland onto the seal, on the unprepared
fieldbus cable

Strip fieldbus cable here

Draw back the shielding braid
over the sheath of the fieldbus cable

Type

Cat. No.

Profibus PA T distributor type FBCon PA CG/M12 1way EX

8564150000

Profibus PA T distributor type FBCon PA CG/M12 2way EX

8564160000

Profibus PA T distributor type FBCon PA CG/M12 4way EX

8564170000

Profibus PA T distributor type FBCon PA CG/M12 8way EX

8564250000

Profibus PA T distributor type FBCon PA CG 1way EX

8564180000

Profibus PA T distributor type FBCon PA CG 2way EX

8564190000

Profibus PA T distributor type FBCon PA CG 4way EX

8564200000

Profibus PA T distributor type FBCon PA CG 8way EX

8564240000

Bus terminating resistor see page 62

With the EEx (ia) version an external bus terminator is necessary at the end of the bus system

Ordering data

The PROFIBUS-PA

is an open field-bus standard
(EN 50 170, IEC 1158-2, DIN 19 245).
It was specifically developed for the re-
quirements of the Process Industry techno-
logy, in particular remote supply and
intrinsic safety. PROFIBUS-PA permits
several PA sensors and actuators to be
operated on one common bus. The devices
are supplied with power via 2-wire techno-
logy with the process data communication
being executed digitally.

Integration into the PROFIBUS-DP net-
work is carried out by means of a
Segment Coupler. Specific advantages of
PROFIBUS-PA :

• Reduced wiring costs

• Minimised design costs of the

process control system

• Remote interrogation and programming

of field devices

• Intrinsically safe version for applications

in potentially explosive atmospheres.

• Continuing development and support

through the PROFIBUS User and Trade
Organisation (PNO)

Use ferrules!

Weidmüller offers here the PROFIBUS-PA FB-Connector. In the event of service or plant modification,
the PROFIBUS-PA FB-Connector from Weidmüller permits the connection or replacement of field devices without interrupting the bus
system. Extensive accessories as well as preassembled cables and plugs round off the program.

Customer-specific solutions on request