Technical data kld2-gt-dp.1pa – VEGA KLD2-GT-DP.1PA Gateway for PROFIBUS DP-PA segment coupler SK2 User Manual

Page 2

Advertising
background image

2

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

Technical Data

KLD2-GT-DP.1PA

096

76

5_

EN

G.xm

l

2

003

-02-

2

7

Supply

Connection

Power Rail or terminals +, -, FE

Rated voltage

20 ... 35 V DC

Ripple

≤ 10 %

Rated current

138 mA ... 84 mA (without load)

Power loss

3 W

Fieldbus connection

Profibus DP

1 RS485 interface

Connection

9-pin sub-D socket

Baudrate

45,45 kBit/s ... 12 MBit/s

Protocol

PROFIBUS DP V1

Connection to power link

Connection

Power Rail or terminals CH1+ at 28+, CH1- at 29- of KLD2-PL1.PA
Power Rail or terminals CH1+ at 40+, CH1- at 41- of KLD2-PL-Ex1.PA

Baudrate 31,25

kBit/s

Electrical isolation

CH/PROFIBUS DP

function insulation, rated insulation voltage 50 V

eff

PROFIBUS DP/Supply

function insulation, rated insulation voltage 50 V

eff

All circuits/FE

function insulation, rated insulation voltage 50 V

eff

Standard conformity

Electrical isolation

EN 50178

Electromagnetic compatibility

NAMUR NE 21

Protection degree

IEC/EN 60529

Fieldbus standard

EN 50170/2

Climatic conditions

DIN IEC 721

Directive conformity

Electromagnetic compatibility

standards

Directive 89/336/EG

EN 61326, EN 50081-2

Ambient conditions

Classification

3K3

Ambient temperature

-20 ... 60 °C (253 ... 333 K)

Relative humidity

< 75 %

Degree of soiling

max. 2, according to IEC 664

Mechanical specifications

Connection type

terminals

Core cross-section

up to 2.5 mm

2

Housing

60 mm x 115 mm x 107 mm

Protection degree

IP20

Mass 600

g

Mounting

DIN rail mounting

Data for application in conjunction with
hazardous areas

Statement of conformity

TÜV 02 ATEX 1819 X

Group, category, type of protection,
Temperature classification

¬ II 3 G EEx nA II T4

Connection to power link

Connection to the data interface CH of KLD2-PL-Ex1.PA (Konf. TÜV 00 ATEX 1531X)
Connection to the data interface CH of KLD2-PL-1.PA (Konf. TÜV 00 ATEX 1788X)

Directive conformity

standards

Directive 94/9 EU

EN 50021

Operating principle
Together with at least one power link, the gateway forms a segment coupler for connecting a PROFIBUS PA segment to the PROFIBUS DP.
The PROFIBUS is standardised to EN 50 170/2. The gateway supports all transfer rates thus defined up to 12 MBit/s.
The gateway can make one, two or four channels available. The channels work completely independently of each other in terms of time. This
makes it possible to reduce response times considerably. Up to 5 power links can be connected to each channel, of which each forms its own
PROFIBUS PA segment.
Communication between the gateway and the power links takes place over the power rail for Channel 1 and over the terminals for the other
channels.
The communication process is transparent. Each PA station is addressed directly and planning for them is like a PROFIBUS DP station. The
planning does not include the gateway and power links.
The gateway can be mounted in Zone 2. Power Links are also permitted for this type of installation.
Version KLD2-GT-DPR.xPA allows for operation with a redundant transmission line on the PROFIBUS DP side.
The channels work directly at 31.25 kBaud (Manchester coded). This saves additional delay times in the power links.
For additional information, please consult the segment coupler manual/operating instructions (Part. No. 105085).