Milton CAT C27 Sub-Base Fuel Tank Base User Manual

C27 sub-base fuel tank base, Features description, Options

Advertising
background image

A T T A C H M E N T S

LEHE7416-00

FEATURES

DESCRIPTION

C27 SUB-BASE
FUEL TANK BASE

Griffin

Diesel Generator Set
750-900 kVA 50 Hz
650-800 kW 60 Hz

●

UL 142 listed

●

Designed and built to comply with NFPA 30,
37, 110

●

Tank design provides capacity for thermal
expansion of fuel

●

Direct reading fuel level gauge

●

Fuel supply dip tube is positioned so as not
to pick up fuel sediment

●

Fuel return and supply dip tubes are separated
by an internal baffle to prevent recirculation
of heated return fuel

●

Fuel fill – 101.6 mm (4 in), lockable flip top cap

●

Primary tank level detection switch in
containment basin

●

Primary and secondary tanks are leak tested
at 20.7 kPa (3 psi) minimum

●

Welded steel containment basin (minimum
of 110% of primary tank capacity)

●

Interior tank surfaces coated with a solvent-
based thin-film rust preventative

●

Heavy gauge steel gussets suitable for lifting
package

●

Gloss black polyester alkyd acrylic enamel
exterior paint over epoxy based primer

●

Primary tanks are equipped with customer
connections for remote fuel transfer, return
and vent

●

Dual wall, secondary containment

●

Heavy construction 6 mm (0.24 in) steel plate
side channels and 4 mm (0.16 in) sheet steel
tank design

●

Rear and right side stub-up access

●

Emergency vents on primary and secondary
tanks are sized in accordance with NFPA 30

●

Leak detection switch

●

Compatible with enclosures (weather
protective and sound attenuated)

●

The sub-base fuel tank mounts below the
generator set wide base

OPTIONS

●

Manual fuel transfer pump

●

Low fuel level switch (alarm and shutdown)