Velleman VTSSC70 User Manual

Page 5

Advertising
background image

VTSSC70

18.02.2010

©Velleman nv

5

7. Operating Temperature

The most common soldering alloys used in the electronics industry consist of 60% tin and 40% lead. The

operating temperature of this type of solder is detailed below and can vary from manufacturer to

manufacturer. However, to meet RoHS requirements, these solders are no longer allowed and are

replaced by lead-free solders that require a working temperature which is ±30°C (54°F) higher.

leaded

solder lead-free

Melting point

215°C

(419°F)

220°C (428°F)

Normal Operation

270-320°C (518-608°F)

300-360°C (572-680°F)

Production Line Operation

320-380°C (608-716°F)

360-410°C (680-770°F)

A good joint is assured if the iron's operating temperature is set within the parameters suitable for the

type of solder being used. The solder will flow too slowly if the temperature is too low; if the temperature

is too high, the flux in the solder may burn which will give rise to billowing white smoke. In turn, this will

result in a dry joint or in permanent damage to the PCB.

8. Operating instructions

Refer to the illustrations on page 2 of this manual.
Verify whether the operating voltage of the unit is identical to that of the electrical supply.
GENERAL

Make sure the unit's power switch [6] is in the "OFF"-position.

Plug in the soldering iron [5]. Note that the connector has a notch so it only fits in one way. Do not

force.

Connect the AC power cord to the power connector [7]. Connect the other end to a suitable mains

outlet.

When applicable, connect an earth wrist strap to the earth jack [9] at the back of the station.

PARAMETER SETTINGS

Switch on the station [6]

Press the SET-button [2] and hold for at least

5 seconds until the display shows “— — —”

(flashing).Use the ▲-button [4] to enter the mode lock password “010” (default) and press the set-

button [2] to go into setup menu. A wrong password will return to normal working mode

(temperature indication).

In the setup menu, the display will show “F-0”. Press the ▲[4]- or ▼ [3]-button to select modes. If

no button is pressed within 15 seconds the device will return to normal operation mode.

F-0: exit menu mode

Press the SET-button [2] when the display shows F-0 to exit the setup menu and return to

temperature indication.

F-1: password mode

When password mode is enabled, the user can not change the temperature settings on the

station unless he or she knows the password.

Press the set-button [2] once to enter password mode. Press the ▲[4]- or ▼ [3]-button to

change display between 000 and 100, with 000 indicating password mode disabled and 100

indicating password enabled. Press the set-button [2] to return to the setup menu.

F-2: temperature correction mode

Press the set-button [2] once to enter temperature correction mode. Press the ▲[4]- or ▼ [3]-

button to enter a correction factor for the temperature, e.g. when the display shows 300°C but

the actual temperature is only 290°C, add 10°C to the shown correction value.

When in °C negative values are indicated with a minus in front; in °F negative values are

indicated by a blinking display (5s interval). Press the set-button [2] to return to the setup

menu.

F-3: unit of temperature

Press the set-button [2] once to enter temperature mode. Press the ▲[4]- or ▼ [3]-button to

change between °C and °F. Press the set-button [2] to return to the setup menu.

Advertising