UPS Status Display String Description:

The following table shows the description of the LCD display string:

Table4. UPS Status Display String

LCD Display String

Description

STbY

UPS work at Standby mode

IPVL

Input voltage is too low

IPVH

Input voltage is too high

IPFL

Input frequency is too low

IPFH

Input frequency is too high

NORM

UPS work at Line mode

AVR

UPS work at AVR mode

bATT

UPS work at Battery mode

TEST

UPS work at battery life/function test mode

OPVH

Battery mode, the output is too high

OPVL

Battery mode, the output is too low

OPST

Output short

OVLD

Overload

bATH

Battery voltage is too high

bATL

Battery voltage is too low

OVTP

Internal temperature is too high

FNLK

Fan is locked

bTWK

Batteries are weak

User Setting String Description:

The following table shows the options that can be changed by user.

Table5. User Setting String

OPV

Output voltage mode select

[220]= 220V
[230]= 230V
[240]= 240V

AVR

Input type select

[000]= Normal range mode
[001]= Wide range mode
[002]= Generator mode

EbM

External battery module
(EBM)

0~9 is the number of external battery
module

TEST Auto self-test

[000]=Disable [001]=Enable

AR

Automatic restart

[000]=Disable [001]=Enable

GF

Green function

[000]=Disable [001]=Enable

bZ

Buzzer control

[000]=Disable [001]=Enable

LS1

Load segment 1

[000]=Turn off [001]=Turn on

LS2

Load segment 2

[000]=Turn off [001]=Turn on