2 converter function, 3 parallel function – PowerWalker VFI 6000T LCD User Manual

Page 44

Advertising
background image

41

6.2 Converter Function

6.2.1 Brief introduction of Converter function

In converter mode, the UPS would free run with fixed output

frequency (50Hz or 60Hz). Once the mains power is loss or

abnormal, the UPS would transfer to Battery mode and the load is

supplied continuously.

The great virtue is the output frequency is fixed, which is required by

some very sensitive loads.

But the disadvantage is the load capacity of UPS should be derated

to 60% in converter mode.

6.2.2 Set the function

The function could be enabled through the LCD setting in Bypass

mode.

Enter the power strategy setting menu by following chapter of 5.4.7.

6.3 Parallel Function

6.3.1 Brief introduction of the redundancy

N+X is currently the most reliable power supply structure. N

represents the minimum UPS number that the total load needs, X

represents the redundant UPS number, i.e. the fault UPS number

that the system can handle simultaneously. When the X is larger, the

reliability of the power system is higher. For occasions where

reliability is highly depended on, N+X is the optimal mode.

As long as the UPS is equipped with parallel cables, up to 4 UPSs

can be connected in parallel to realize output power sharing and

power redundancy.

Advertising