PowerWalker VFI 6000T LCD User Manual

Page 51

Advertising
background image

48

Over Charge

Battery is over

charged

The UPS will turn off the

charger until the battery voltage

is normal

Model Pin Error

UPS internal fault

Consult dealer.

Ambient Over

Temperature

The ambient

temperature is too

high

Check the environment

ventilation.

Heatsink Over

Temperature

Inside temperature of

UPS is too high

Check the ventilation of UPS

and the ambient temperature.

Ambient NTC abnormal

UPS internal fault

Consult dealer.

Para Cable Male Loss

The parallel cable is

disconnected

Check the parallel cable.

Para Cable Female

Loss

The parallel cable is

disconnected

Check the parallel cable.

Para Bat Differ

The battery packs of

some UPSs are

disconnected

Check if all the battery pack is

connected.

Para Line Differ

The mains input of

some UPSs is

disconnected

Check the building wiring and

input cable.

Check if the input breaker is

closed.

Ensure the UPSs are

connected to same input

source.

Para Work Mode Differ

There are different

power strategy setting

in parallel system

The UPSs with different power

strategy setting (Ex. one Line

mode and one Converter mode)

are forbidden to parallel.

Para Rate Power Differ

There are different

UPSs in parallel

system

The UPSs with different

capacity (Ex. one 6KVA and

one 10KVA) are forbidden to

parallel.

ECO In Para

HE function is

enabled in parallel

system

HE function is forbidden in

parallel system.

IP Fuse Open

Input fuse break

Check the input fuse status

Advertising