All control methods are available without any changes in the hardware or software.
The control mode of inverter is selected by parameter P1.1.11 Input set, which has eight alternative
settings: MS2 (stop-limit), MS2/MS3 (slow-limit), EP2 (stop-limit), EP2 (slow-limit), EP3, MS4, MS5 and
AU (automation control). (See Chapter 5: parameter descriptions.) The parameter assigns digital inputs
S1, S2 and DID3-DID5. It is not possible to change the functions of the inputs separately. Digital inputs
DID1 and DID2 are for direction commands, so DID1 = S1, DID2 = S2 in every case. Digital inputs (DID3-
DID5) are automatically assigned according to the selected mode. In mode MS5, the MAX speed will be
activated when DID4 is off and DID5 is still on. The state of inputs can be checked from parameter V2.3.

Control Mode

MS2 (stop-lim) MS2 (slow-lim) EP2 (stop-lim) EP2 (slow-lim) EP3

MS4

MS5

AU (Ain1)

Parameter

P1.1.11

0 1 2 3 4

5

6

7

Signal

Terminal

S1

X1:38

S1 S1 S1 S1 S1

S1

S1

S1

S2

X1:39

S2 S2 S2 S2 S2

S2

S2

S2

DID3

X1:40

MAX MAX AP AP AP

MS2

MS2

S11/S21

DID4

X1:41

S12 S11/S21

S12 S11/S21

HOLD

MS3

MS3/MAX

S12

DID5

X1:42

S22 ES S22 ES S11/S21

MAX

MS4

S22

S1

Drive command forward

S2

Drive command reverse

AP

Acceleration command

HOLD

Hold speed command

S11

Slowdown limit forward

S21

Slowdown limit reverse

S12

Stop-limit forward

S22

Stop-limit reverse

S11/S21

Common slowdown limit

MS2

Multistep Frequency2

MS3

Multistep Frequency3

MS4

Multistep Frequency4

MAX

Maximum frequency

ES

External stop


Desired speed levels for multi-step control mode are selected with following parameters

Speed Parameter

Input

Speed 1

P1.1.4

S1/S2

Speed 2

P1.1.8

MS 2

Speed 3 (only available in MS4) P1.1.9

MS 3

Speed 4 (only available in MS5) P1.1.10

MS 4

Speed 5

P1.1.5

MAX

2.6.1 MS2-control

c_coms2a

A. Pushbutton / controller position
B. Speed

0)

“decelerate to zero”

1)

step 1 “drive minimum speed”

2)

step 2 “drive maximum speed”