Adjusting the Flux Shifter
With the breaker in the CLOSED position, the gap
between the adjustment screw and the trip paddle should
be
1
/
32
inch, as shown in Figure 9. For safety, OPEN the
breaker before adjusting the screw with a
1
/
4
-inch
wrench. CLOSE the breaker to check the adjustment.
WARNING: Be extremely careful when working on a
CLOSED breaker. Do not reach into the mechanism
while adjusting the flux shifter.
Optional Test – The flux shifter may be tested by closing
the breaker and applying a 9 Vdc power source to the
flux shifter leads (the red wire is positive). The breaker
should trip.
Figure 8. Trip unit mounting bracket installed on the
breaker frame.
Figure 9. Adjusting the flux shifter.