DISCHARGE on a white background. If installing 
in a draw-out type breaker remove breaker from 
adaptor (cassette) before continuing. 
 
3. Loosen the 6 screws on front cover (fascia) 
using a posidrive screw driver as shown in Fig 1.B 
Rotate the charging handle down and slide the 
front cover over the handle to remove the front 
cover as shown in Fig. 1.C. 
 
Figure 1. (A) Front Cover (B) Screw Removal (C) Handle 
Rotation 
 
 
4. Slide the RTC switch assembly over the 
mechanism side sheet and locate in the two 
locating holes as shown in fig 2. 
 
Figure 2. Assembly on mechanism
 
 
5. Assemble the screw with washer as shown in 
Fig. 3 Tighten the screw to torque 1.2Nm (0.9 ft-
lbs). 
Figure 3. Screw assembly 
 
6. When RTC thru trip unit is used, plug the 
connector from the RTC switch assembly to the 
connector marked as RTC from the harness of the 
trip unit as shown in Fig. 4. 
Figure 4. Connector Plug Assembly
 
7. If RTC is used thru the secondary disconnect, 
then first unplug the spring charge contact 
connector from motor as shown in Fig. 5 
 
Figure 5. Unplug Spring Contact
 
7. Plug the connector from the RTC switch 
assembly with the plug marked as RTC as shown 
in fig 6. 
 
2