3 charging motor – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac Maintenance Manual User Manual

Page 51

Advertising
background image

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 8. Accessory Maintenance

41

8.3 Charging Motor

The Charging Motor provides a means of electrically

charging the springs that close the breaker. The Charging

Motor is available only as a factory-installed option. It is

always provided on electrically operated breakers.
The circuit breaker closing springs are charged automati-

cally when control voltage is applied to terminals 8 and 17

of the secondary disconnects. When the springs are fully

charged, a cutoff switch automatically de-energizes the

motor. The closing springs will recharge automatically

after the breaker closes.
Renewal parts for the Charging Motor are the motor and

the cut-off switch, illustrated in Figure 51. The catalog

number and electrical characteristics of the Charging

Motor are listed in Table 8.

Figure 51. Charging Motor and cut-off switch.

Catalog

Number

Voltage

Range, Vac

568B596G5 104–127

Table 8. Catalog number and operating voltage for the Charging Motor

accessory.

Removing the Charging Motor

Use the following procedure to remove the Charging

Motor for replacement, as illustrated in Figure 52.

1. Carefully place the breaker on a suitable working

surface, so that the right front of the breaker is

accessible.

2. Disconnect the motor wires at the connector.
3. Remove the three bolts and lock washers securing

the motor to the breaker mechanism.

4. Remove the motor and the three mounting spacers.

Installing the Charging Motor

Use the following procedure to install a replacement

Charging Motor, as illustrated in Figure 52.

1. Place the motor in position with the three mounting

spacers on the breaker mechanism and insert the

three mounting bolts and lock washers. Tighten the

bolts to 110 in-lb.

2. Connect the motor wires by plugging the connector

into place.

Removing the Motor Cut-Off Switch

Use the following procedure to remove the motor cut-off

switch, as illustrated in Figure 52.

1. Carefully place the breaker on a suitable working

surface, so that the right front of the breaker is

accessible.

2. Remove the breaker escutcheon, as described in

Section 7.5.

3. Disconnect the wires at the screw terminals on the

switch.

4. Remove the nut from the switch stem under the

hole in the mounting bracket.

5. Remove the cut-off switch.

Installing the Motor Cut-Off Switch

Use the following procedure to install the replacement

motor cut-off switch, as illustrated in Figure 52.

1. Screw one of the locking nuts onto the switch barrel

and place the flat washer over the nut.

2. Place the cut-off switch in position with the switch

stem through the hole in the mounting bracket.

Attach the mounting nut and secure the switch.

3. Connect the wires at the screw terminals on the

switch.

Advertising