5.2.20 Supported data types
Value
Data Type
3
Integer16
4
Integer32
5
Unsigned8
6
Unsigned16
7
Unsigned32
9
Visible string
10
Octet string (byte string)
33
N2 (standardised value)
35
V2 (bit sequence)
44
Error
54
Time difference without date indication
5.2.21 Value
The value field contains the parameter value of the request. When the response is negative, the field contains a corresponding error code. If the values consist
of an odd number of bytes, a zero byte is appended in order to maintain the word structure of the messages.
For a positive partial response, the parameter value field contains the following attributes:
Format = (Data Type or Byte, Word, Double Word)
Number of values = actual number of values
Value = Parameter value
For a negative partial response, the parameter value field contains the following:
Format = error (44H)
Number of values = 1
Value = error value = error number