GE Industrial Solutions SPSA600 User Manual
Page 8
 
GEH-6251 Installation Instructions
Connections
The screw terminals on the Power Supply Plate are 
labeled by function for clarity. The terminal strip 
pockets on the AC INPUT fuse block will accommodate 
a spade lug or ring terminal with a tongue width up 
to 0.45 inches. The terminal screw size is 10-32. The 
terminal strip pockets on the Power Supply Assembly 
will accommodate a spade lug or ring terminal with 
a tongue width up to 0.320 inches. The terminal 
screw size is 10-32. To make the connection, attach 
an appropriate spade lug or ring terminal to the wire, 
then slip the fastener beneath the terminal screw and 
tighten. The Power Supply Plate also contains two 
12-pin plug connectors. The connectors are keyed 
so they cannot be inserted incorrectly into a mating 
12-pin receptacle connector. To connect to the Power 
Supply Plate plug(s), align the receptacle interlock 
connector of a Distribution Cable Harness with the 
plug hook connector of the Power. Supply Plate. Insert 
the receptacle until the interlock and hook catch (see 
Figure 6). To disconnect from the Power Supply Plate, 
press down at the rear of the receptacle interlock until 
the interlock clears the plug hook and withdraw the 
receptacle interlock (see Figure 7).
Figure 6. Slide view of receptacle-plug insertion into the Power
Supply Plate.
Figure 7. Side view of receptacle-plug removal from the Power
Supply Plate
Parts And Options
The only user-serviceable components or parts 011 
the Power Supply Plate are the fuses in the AC INPUT 
fuse block. The fuses listed in Table 4 are recommended 
as replacements for use with the Power Supply Plate. 
Failure to use the proper type of fuses can result in 
damage to the Power Supply Plate. Two fuses per 
Power Supply Plate are required. If you prefer to 
purchase a +24Vdc Power Supply without the factory 
mounted AC line fuses or a control power transformer, a 
Power Supply Assembly is available. This Power Supply 
Assembly always requires AC line fuse protection and 
in applications where the AC input voltage is greater 
than 240Vac @ 60 Hz, a control power transformer 
will always be required to step the voltage down to 
85-240Vac @ 60 Hz. Table 5 lists the details on the GE 
Power Supply Assembly.
Table 4. Recommended Replacement Fuses for use with the
Power Supply Plate
Ampere
Rating
Catalog
Manufacturer
Number Comments
2 amp
Gould-Shawmut ATMR 2
Class CC current 
limiting fuse
Table 5. Available GE Power Supply Assembly
Catalog
Number
Description
AC Line Fuses
Requirement
Voltage Rating of
Assembly
SPSAA
Power Supply
Assembly
2 amp class CC
85Vac to 240Vac
@50/60 Hz