Table 1 Rectifiers and Converters
Rectifier/Converter
Input
Output
Eco Compatible
Eco Rectifier
blue
NE050ECO48ATEZ
ac 110/208/220/240 Vac
dc 60Vdc (+/-30V)
to 310Vdc (+/-150)
11A max
48V, 50A
Yes
Eco Rectifier
orange
NE100ECO24TEZ
ac 110/208/220/240 Vac
dc 60Vdc (+/-30V)
to 310Vdc (+/-150)
11A max
24V, 100A
Yes
Converter
blue
NE040DC48ATEZ
24 Vdc
48V, 40A
Yes
NE030DC48A
48V, 30A
Yes
Converter
orange
NE075DC24A
48 Vdc
24V, 75A
Yes
Rectifier
blue
NE075AC48ATEZ
110/208/220/240 Vac
48V, 75A
AC Only
NE050AC48ATEZ
110/208/220/240 Vac
48V, 50A
NE050AC48A
208/220/240 Vac
Rectifier
orange
NE100AC24ATEZ
110/208/220/240 Vac
24V, 100A
AC Only
NE100AC24A
208/220/240 Vac
NE850 Slot Filler
7
REQUIRED – Eco rectifiers in all DC (PV or solar) powered rectifier positions.
RECOMMENDED – Eco rectifiers in all Eco system rectifier positions.
NOT RECOMMENDED – non-Eco rectifiers in Eco systems.
Non Eco rectifiers will not function properly when powered by DC (PV or solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling all system rectifier positions.
Non Eco rectifiers may be installed in AC powered rectifier positions of Eco systems.
8
44A with 120Vac input
9
22A with 120Vac input
10
NOT RECOMMENDED for use in Eco systems - Non Eco rectifiers will not function properly when powered by DC
(PV or solar) input in Eco systems.
Use of non-Eco rectifiers in Eco systems increases the risk of improperly filling system rectifier positions.
11