ASTAT-CD Plus Service Instructions

30

Troubleshooting Guide for ASTAT-CD Plus Solid-State Starters

Symptom or Error & (Error Code) Possible Cause

Measures to be taken

Display OFF

No control voltage

Check wire harness and control voltage

Main breaker tripped or fuse blown

F1 fuse blown on power supply PCB

Check and change

Bad connection of flat ribbon wire

Verify connectors

joining power supply PCB to control PCB Check power supply board and logic board for 5VDC.

Use a DC voltmeter on the power supply board, (-) lead

of voltmeter on the top lead of C6 (located next to the

black heatsink on the right edge of the power supply

board) and the (+) lead of voltmeter on top lead of

Diode AD21 or R25 (located on the upper right corner

of the power supply board)

Fans not running

No voltage to fans

Verify voltage and connections

Equipment does not respond to

F2 fuse blown on power supply PCB

Check and change

STOP / START controls

Motor will not start but display

No power to gate circuits

Check 12VDC on Power Supply Board. Use a DC

shows – Ramp, Full, etc.

voltmeter on the Power Supply Board, (-) lead of

voltmeter on the top lead of C6 (located next to the

black heatsink in the right edge of the Power Supply

Board) and the (+) lead of voltmeter on bottom lead of

Diode AD20 (located near the lower left corner of the

black heatsink on the Power Supply Board).

Frequency error (Ex10)

No 1L1 phase or

Check 1L1 phase and/or

(admits 45Hz

f main

65Hz)

frequency is out of range

mains frequency

Overload trip (Ex11) Excessive load or excessive current

Verify overload conditions during starting time and

during starting

steady state. Check settings in parameters "Nxxx",

"Lxxx", and "oxxx"

Synchronism loss (Ex13) Phase 1L1 lost Check

1L1 phase

Phase A, B, C thyristor (Ex14) Short circuited thyristor

Check thyristor module

(Ex15)

Check ground connections and voltage to ground

(Ex16)

Poor ribbon cable connection

No output phases

Check 2T1, 4T2 and 6T3 phases

Heatsink thermostat (Ex17) Heatsink thermostat tripped by

Check for adequate ventilation

overheating or defective

Check thermostat and wiring

Motor thermistor (Ex18) Motor thermistor tripped by

Check thermistor and wiring, if no thermistor terminal

overheating or defective

5 and 6 must be jumpered

PULSE
TRAFO

PULSE
TRAFO

PULSE
TRAFO

MAIN

TRANSFORMER

F2

F1