F702
BITFIELD
SRCx Node System Diagnostics 1
0
Node not receiving a broadcast message from CPU A
1
Node not receiving a broadcast message from CPU B
2
No link pulse from CPU A
3
No link pulse from CPU B
4
Invalid system frequency received from CPU A
5
Invalid system frequency received from CPU B
6
Invalid IOC pickup setting multiplier received from CPU A
7
Invalid IOC pickup setting multiplier received from CPU B
8
Invalid ST setting received from CPU A
9
Invalid ST setting received from CPU B
10
Invalid GF setting received from CPU A
11
Invalid GF setting received from CPU B
12
Invalid command received from CPU A
13
Invalid command received from CPU B
14
CPU A command not completed due to arbitration
15
CPU B command not completed due to arbitration
F703
BITFIELD
SRCx Node System Diagnostics 2
0
CPU A command timed out
1
CPU B command timed out
2
Node synch not locked
3
Unknown Message Received on Port 0
Format Name Format Type/Bitmask
Format Definition