GE Industrial Solutions MicroVersaTrip Plus and MicroVersaTrip PM AK-25 and AKU-25 User Manual

Page 6

Advertising
background image

6

SECTION 3 TESTING AND

TROUBLESHOOTING

Once the breaker has been converted, but before it

is energized, it must be tested. See below for

testing and troubleshooting details.

Testing

Before installing a converted breaker back into

service, perform the following steps:

Step 1.

Verify that the programmable trip unit is securely

installed by performing a continuity test on the CT

wiring and programmer. Disconnect the black CT

wires at each phase sensor. Then using a

continuity tester or V.O.M., check for continuity

from the white CT wire lead of the phase “A” CT

to the white CT wire lead of the phase “B” CT.

Repeat this continuity test for the white CT wire

leads of phase “A” and phase “C”. Next, measure

the resistance across each phase sensor and

compare the values measured to the values listed

in table 3-1. Be sure to reconnect the black CT

wire leads to all of the phase sensors prior to

performance testing the breaker.

CAUTION: In addition to the continuity test

described above and prior to performance test-

ing the converted breaker, each phase of the

breaker should be primary injected with a current

level of about 10% but no more than 20% of the

CT rating. During the application of test current,

the programmer’s screen should be activated by

depressing the battery button on its face and

check that the test current is displayed on the

screen for each phase tested. This test along

with the continuity test will confirm that no open

circuits exists in the CT harness and that the trip

unit is mounted properly. If the programmer

fails to display the test current, the test should be

stopped immediately and the programmer/wire

harness installation should be verified prior to

proceeding with any additional testing.

WARNING: IF THE CONVERTED BREAKER IS

ENERGIZED OR PRIMARY INJECTED USING A

SUFFICIENT LEVEL OF TEST CURRENT WITH A

LOOSE OR OPEN CIRCUIT BETWEEN THE CT’S

AND THE PROGRAMMER, DAMAGE WILL

OCCUR TO THE PROGRAMMER UNIT, WIRE

HARNESS, 36-PIN PROGRAMMER CONNECTOR

AND CT’S. FAILURE TO ADHERE TO THESE

INSTRUCTIONS WILL VOID ALL WARRANTIES.

Step 2.

Meggar the breaker primary circuit using a

1,000-Volt Meggar.

Step 3.

Measure the resistance across the line and load

terminals for each phase using a Micro-Ohmmeter

or Milli-Volt tester. If the resistance differs

considerably from phase to phase, the electrical

points may not be properly tightened. Also, it may

indicate improper contact wipe.

Step 4.

To verify that the breaker has been properly

retrofitted, a primary injection test should be

performed on each phase. This test will check the

CT’s, bus, wiring harness, flux shifter, and trip unit

as a complete system. A high current, low voltage

power supply should be connected across each

line and load terminal to simulate an overcurrent

fault. The long-time may be set at 0.5 to minimize

the breaker stress. When ground fault is installed,

the test can be performed by wiring two adjacent

poles in series or by using the GE test kit Cat. No.

TVRMS2. This will prevent the breaker from

tripping due to an unbalanced current flow.

Do not attempt to use GE test kit Cat. No.
TVTS1 or TVRMS on this programmer.

Troubleshooting

When malfunctioning is suspected, first examine

the circuit breaker and its power system for

abnormal conditions such as:

1. Breaker tripping in proper response to

overcurrents or incipient ground faults.

2. Breaker remaining in a trip-free state due to

mechanical interference along its trip shaft.

3. Inadvertent shunt trip activation’s.

WARNING: DO NOT CHANGE TAPS ON THE

CURRENT SENSORS OR ADJUST THE

PROGRAMMER TRIP UNIT SETTINGS OR

REMOVE THE PROGRAMMER TRIP UNIT WHILE

THE BREAKER IS CARRYING CURRENT.

FAILURE TO ADHERE TO THESE INSTRUCTIONS

WILL VOID ALL WARRANTIES.

Advertising