Accessory kit installation, Overload relays, Starter wiring diagram installation – GE Industrial Solutions CR454A Series Starters User Manual

Page 3

Advertising
background image

CR453A Accessories

Standard

Accessory

Contacts

(with quick connects on

C-2000

side-mount accessories) accessories

600V side-mount aux.

1NO-1NC

CR453XC611

BCLL11

contact block

2NO

CR453XC620

BCLL20

250V side-mount aux

1 SPDT

CR453XC211

contact block

2 SPDT

CR453XC222

600V front-mount aux.

1NO

BCLF10

BCLF10

contact block

1NC

BCLF01

BCLF01

Mechanical interlock,

side-mount

2NC CR453XM602 BEL02

Accessories

Check for Welded Contacts in Overload Relay

Disconnect power from device and control wiring from the

terminals of the relay. Connect the bell set or resistance-

measuring instrument across the relay terminals. Depress

and release the reset arm to ensure the relay is reset. In this

condition there should be continuity between the terminals.

In the tripped condition, the circuit between the terminals

should be open indicating the contacts are operating

normally. Remove the bell set or resistance measuring

apparatus, rewire the relay terminals and reset the relay for

normal operation.

For further technical details on overload relays, refer to

installation instructions GEH-6237A.

Accessory Kit Installation

Overload Relays

C

NC

N

C

NC

N

C

C

NC

N

NC

N

C

NC

N

NC

C

N

33

34 44

43

32 44

31 43

22

14

13

14

21

24

13 23

L1

L2

L3

T1

T2

T3

OPTIONAL
AUX
CONTACTS

OL-THERMAL OVERLOAD RELAY

NO-NORMALLY OPEN
NC-NORMALLY CLOSED

AUX CONTACT OPTONS

TYPE

LEFT
SIDE

RIGHT
SIDE

1 SPDT

2 SPDT

2 NO

1 NO-1 NC

M

OPTIONAL
AUX
CONTACTS

FRONT VIEW

MOTOR

M-LINE CONTACTOR

NOMENCLATURE

SPDT-SINGLE POLE DOUBLE THROW

ELEMENTARY

96

95

1

REMOTE
CONTROL

L1

L2

OL

M

CONTROL CIRCUIT FUSING

(IF USED)

L1

L2

1

96

NOTE: ADDITIONAL CONTROL CIRCUIT PROTECTION
MAY BE REQUIRED.PREFER TO NATIONAL
ELECTRIC CODE OR LOCAL CODES.

FOR SEPERATE CONTROL SOURCE-OMIT WIRES A AND B.
CONNECT CONTROL SOURCE TO 1 ON CONTROL DEVICE.
AND 96 ON OVERLOAD RELAY.

CONTROL

REMOTE

1

L1

L2

L3

95

96

97

98

WIRE B

WIRE A

Starter Wiring Diagram

Installation

Catalog No.

Current Range (A)

Contactor

Class 10

Class 20

RT1B

RT12B

0.16-0.26

RT1C

RT12C

0.25-0.41

RT1D

RT12D

0.4-0.65

RT1F

RT12F

0.65-1.1

RT1G

RT12G

1.0-1.5

RT1H

RT12H

1.3-1.9

RT1J

RT12J

1.8-2.7

CR453AB, RT1K

RT12K

2.5-4.1

AC, AD

RT1L

RT12L

4.0-6.3

RT1M

RT12M

5.5-8.5

RT1N

RT12N

8-12

RT1P

RT12P

10-16

RT1S

RT12S

14.5-18

RT1T

RT12T

17.5-22

RT1U

RT12U

21-26

CR453AC, AD

RT1V

RT12V

25-32

CR453AD

RT1W

RT12W

30-40

Typical 250V side auxiliary contact kit.

Typical 600V side auxiliary contact kit.

Advertising