EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH-41549 02/12

Figure 9. Modify Bracket

Steps for removing the bracket pin:

1. Remove the left bracket assembly (75C149309G061) from compartment (

Figure 9

). The assembly is

bolted to the side sheet. Four fixing bolts assembled can be removed by the service technician. For this
task, a socket head wrench or a normal wrench, used for fastening hex bolts, is required.

2. Remove the pin from the bracket (75A106208P204). The pin is riveted from the inside and has to be

drilled from the same side. Removing the bracket is necessary.

3. Note that assembly must be done by a trained service technician only.
4. Apply corrosion resistance treatment to the exposed metal after removing the pin.
5. Reassemble the bracket assembly and scrap or discard the pin.

Install AKD-8—Retrofilll

It must be ensured that the supply power to

the compartment is turned off/

compartment is de-energized for all the

incoming and outgoing circuits of the LVS

prior to any work being conducted on it.

During the installation and related work on

the equipment, it must be ensured that the

operator is using the prescribed PPE for the

specified tasks.

Ensure only qualified personnel install, operate, service, and maintain all electrical

equipment.

After the existing breaker is removed and the compartment modified, the pre-wired Retrofilll breaker can
now be installed in the AKD-8 switchgear.