GE Industrial Solutions EntelliGuard E Circuit Breaker User Manual
Page 25
©2012 General Electric All Rights Reserved
25
Then use this as a pivot and ensure that all four tabs lock in 
place (Fig. 7.6). 
Figure 7.6. Carriage Position Switch Location 
CLUSTERS (PRIMARY DISCONNECT FINGERS) 
Clusters are the main isolating contacts which are installed 
on the rear terminals on the withdrawable circuit breaker. 
Cluster contacts may be easily and quickly removed and 
replaced using cluster pliers (Figs. 7.7 and 7.8). 
 
Figure 7.7. Clusters
Figure 7.8. Cluster Pliers
 
Clusters are mounted vertically through cluster pads for 
different frame sizes. The slot is provided on the terminals 
for locking the clusters. For higher current and short circuit 
ratings, the clusters are assembled in parallel. 
 
MECHANICAL BELL ALARM CONTACT INSTALLATION 
1. Remove the front cover. 
2. Remove the trip unit.
3. Install the mechanical trip alarm as shown in Fig. 7.9.
Figure 7.9. Mechanical Trip Alarm
4. Connect the wires via the plug connectors to the
respective locations of the secondary isolating
contacts A33, A34 and A35 (Fig. 7.10).
Figure 7.10. Plug Connector Location
5. Replace the front cover.
6. Connect the wires via the plug connectors to the
respective locations of the secondary disconnect
contacts A33, A34 and A35.
7. Replace the front cover. 
 
REJECTION FEATURE 
This factory-installed, pin and gate device prevents the 
insertion of a circuit breaker into a cassette if the nominal 
rating of the breaker is incompatible with that of the 
cassette and its ancillary equipment. 
 
Figure 7.11. Rejection Feature 
A Pin block assembly
 
Fig. 7.12 shows the corresponding restrainer assembly 
mounted on the cassette. There are two of these assemblies, 
one on each side of the cassette and the breaker. 
 
Figure 7.12 Corresponding Restrainer