Installation guide, Amp1h5 – GE Industrial Solutions AMP1H5 User Manual
Page 16
TM
AMP1H5
INSTALLATION GUIDE
ZL0115-0A
PAGE 16
©2013 For technical support please contact
01132
DET-785
our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)
Legend
R/W
R=read only; R/W=read or write
NV
Value is stored in non-volatile memory. The value are still available if the meter experiences a power loss and reset.
Units
Lists the physical units that a register holds.
Device Object
Property
R/W
NV
Value Returned
Additional information
Object_Identifier
R/W
NV
Device<n>
n is the 7 digit ID # set in the ID1 & ID2 setup screens on the meter. The BACnet
Device ID is a decimal number from 1 to 4,193,999 that can be entered or viewed
on the user screens or through this property. The default value set at the factory is
a psuedo-random number from 1,000,000 to 3,097,151 to reduce the likelihood of
conflicts if multiple units are installed using their default IDs.
Object_Type
R
NV
Device (8)
Object_Name
R
NV
GE AMP1xx Series Energy Meter - S/N:
<serial number>
Vendor_Name
R
NV
GE Industrial Solutions
Vendor_Identifier
R
NV
276
Model_Name
R
NV
AMP1H5 Energy Meter
Firmware_Revision
R
NV
<Current Revision #>
“xyyy”.
This is the BACnet processor firmware version in the format <xyyy>, with an implied
decimal point between the first two digits (x.yyy)
Application_Software_ Version
R
NV
<Current version #>
“RS= xyyy, OS=xyyy, BACnet Gateway=xyyy”
The format <xyyy> has an implied decimal point between the first two digits (x.yyy)
Location
R/W
NV
<Location>
Limted to 64 Characters - Default value is “Installed location not yet identified”
Description
R
NV
GE AMP1H5 Energy Meter S/N: <serial
number>
Protocol_Version
R
NV
1
BACnet Protocol Version 1
Protocol_Revsion
R
NV
4
BACnet Protocol Revision 4
Local_Date
R
Date
Set via BACnet Time Synchronization only - reverts to Jan 1, 2000 if control power
drops
Local_Time
R
Time
Set via BACnet Time Synchronization only - reverts to 12:00:00 AM if control power
drops
Segmentation_Supported
R
NV
NO_SEGMENTATION (3)
Segmentation is not supported
Max_Master
R/W
NV
1-127 (Factory Default is 127)
Highest possible MAC Address for Master nodes on the local MS/TP network
Max_Info_Frames
R
NV
1
Maximum number of information frames allowed before passing the MS/TP token
Max_APDU_Length_Accepted
R
NV
480
APDU_Timeout
R
NV
60000
Number_of_APDU_Retries
R
NV
0
System_Status
R
NV
Operational (0)
Protocol_Sevices_Supported
R
NV
0b0000000000001011010000000000000
011110000
Protocol_Object_Types_Supported
R
NV
0b1011000010000000000010000000000
Object_List
R
NV
DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI1
0,AI11,AI12,AI13,AI14,AI15,AI16,AI17,AI18
,AI19,AI20,AI21,AI22,AI23,AI24,AI25,AI26
,AI27,AI28,AI29,AI30,AI31,AI32,AI33,AI34
,AI35,AI36,AI37,AI38,AI39,AI40,AI41,AI42
,AI43,AI44,AI45,AI46,AI47,AI48,AI49,AI50
,AI51,AI52,AV1,AV2,AV3,AV4,AV5,AV6,AV
7,AV8,AV9,AV10,AV11,BI1,BI2,BI3,BI4,BI5,
BI6,BI7,BI8,BI9,BI10,BI11,BI12,BI13,BI14,B
I15,TL1,TL2,TL3
Device_Address_Binding
R
NV
{}
Database_Revsion
R
NV
0