Astat-xt rvss panel – GE Industrial Solutions ASTAT-XT RVSS PANEL User Manual
Page 34
DEH40623 - Page 3
AN BL-0464, Rev.02, 04/15/2012
ASTAT-XT RVSS PANEL
Table A
RVSS Panels
– 230 VAC
Wire Sizes and Torque Requirements
Device
RVSS panel Hp
Rating(s)
Minimum Wire Size
Maximum Wire
Size
Required Torque
ASTAT
2 - 25Hp
#18 AWG
# 1/0 AWG
32.7 lb.in.
30 - 60Hp
# 6 AWG
250 MCM
200 lb.in.
75 - 150Hp
(1) 2/0 AWG
600 MCM
375 lb.in.
200 - 250Hp
(4) 3/0 AWG
500 MCM
375 lb.in.
Power Distribution Blocks
2 - 25Hp
#18 AWG
# 1/0 AWG
Note 1
30 - 40Hp
# 14 AWG
# 2/0 AWG
Note 1
50 - 100Hp
# 6 AWG
350 MCM
Note 1
150
# 10 (2) AWG
# 4/0 (2) AWG
Note 1
200
# 6 (2) AWG
350 (2) MCM
Note 1
250
# 4 (2) AWG
500 (2) MCM
Note 1
Control Terminal Board
2 - 250Hp
# 26 AWG
# 10 AWG
Note 1
Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.