3 alarm settings, 4 usage, 5 event logging – GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 90

Advertising
background image

Single-point functions

90

5

5.3.1.3 Alarm settings

Relay Enabled: Select Enabled to enable the relay.

Pickup: Adjust the HRGF pickup from 0.1 Amps to 10 Amps in increments of 0.1 Amp from the
Pickup Setting drop-down menu.

Delay: Adjust the HRGF delay from 0.5 to 5 seconds in increments of 0.1 second from the Time
Delay
drop-down menu.

Ground Resistance: Enter the untapped system ground resistance from 5 to 500 ohms in
increments of 1 ohm.

Figure 5-12 High Resistance GF settings

5.3.1.4 Usage

The High Resistance Ground Fault Relay goes into pickup if the ground current is above the
pickup threshold and generates an alarm if the ground current remains above the threshold for
longer than the delay setting.

5.3.1.5 Event logging

The HRGF relay generates the following events:

Pickup High Resistance GF – when the alarm function enters pickup

Alarm High Resistance GF – when the alarm function operates

Advertising