GE Industrial Solutions EntelliGuard TU Conversion kits User Manual
Page 20
20
5 The wires in harness are color coded for input
and output. Yellow and red wires are for input to
trip unit.
Black and white wires are for output from trip
unit.
6. If required to use the power supply harness for
control power supply, rout the 2-wire harness in
same way above RELT wire harness.
Individual wires in power supply harness are color coded
and numbered. The pins should be inserted at correct
places on backside of 36-pin connector. Refer table 14.
7. Refer Entelliguard
TU Installation manual DEH-
4567 for detailed description of input and output
signal requirements.
Figure 33
Wire Colour
Slot in 36 pin
connector
Function
Red
4
Input +
Yellow
2
Input -
Black
30
Output +
White
27
Output -
Table 12
Wire Colour
Slot in 36 pin
connector
Function
Black
35
24 V DC Supply +
White
36
25 V DC Supply -
Table 13
-
+