Adjusting the Flux Shifter
With the breaker in the CLOSED position, the gap
between the adjustment screw and the trip paddle should
be
1
/
16
inch, as shown in Figure 15. For safety, OPEN
the breaker to adjust the screw with a
1
/
4
-inch wrench.
WARNING: Be extremely careful when working on a
closed breaker. Do not reach into the mechanism while
adjusting the flux shifter.
Optional Test – The flux shifter may be tested by closing
the breaker and applying a 9 Vdc power source to the
flux shifter leads (the red wire is positive). The breaker
should trip.
Figure 15. Adjusting the flux shifter.