MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 2. Setup Mode

18

Instantaneous Pickup

Instantaneous overcurrent protection, with Trip Unit
display illustrated in Figure 19, causes an immediate
breaker trip when the chosen current level is
reached. The pickup value may be set in steps of 0.5
xIn from 1.5 xIn to a maximum dependent on the
frame size and the presence of the short-time
function, as listed in Table 13.

Note the difference from short-time pickup, which is
based on a multiple of

x L T . The time-current

characteristic is shown in Figure 20.

Figure 19. Trip Unit display for instantaneous pickup.

Figure 20. Instantaneous overcurrent protection set point.

F

F

F

Frrrraa

a

am

m

m

meee

e M

M

M

Maa

a

ax

x

x

x.... A

A

A

Am

m

m

mp

p

p

p

R

R

R

Raa

a

attttiiiin

n

n

ng

g

g

g

SS

S

Seee

ettttp

p

p

po

o

o

oiiiin

n

n

nttttssss

W

W

W

Wiiiitttth

h

h

ho

o

o

ou

u

u

utttt SSS

ST

T

T

T

SS

S

Seee

ettttp

p

p

po

o

o

oiiiin

n

n

nttttssss

W

W

W

Wiiiitttth

h

h

h SSS

ST

T

T

T

2000

1.5–10.0

xIn

1.5–15.0

xIn

3200

1.5–10.0

xIn

1.5–13.0

xIn

4000

1.5–9.0

xIn

1.5–9.0

xIn

5000

1.5–7.0

xIn

1.5–7.0

xIn

Table 13. Instantaneous pickup settings for various frame sizes

with and without the short-time function.

On Trip Units with the user-selectable switchable
instantaneous overcurrent and ground-fault option,
X, an additional value of

OFF

appears at the end of

the listing of numerical values. Choose this setting to
disable instantaneous protection. The instantaneous

OFF

selection is interlocked with short-time pickup,

so that only one function can be turned off at a time.

High-Range Instantaneous Overcurrent
Protection

High-range instantaneous overcurrent protection
has a fixed trip setting equal to the breaker frame’s
short-time withstand rating,

H, with pickup tolerance

+0%, –20%. When this option is installed, skip pro-
gramming of instantaneous pickup and go on to the
next function by pressing

SELECT

.

Ground-Fault Pickup

The trip unit display for ground-fault pickup is
shown in Figure 21. This function sets the pickup
current for ground-fault protection. The available
settings are listed in Table 14 as multiples of

xCT the

current sensor rating, in steps of 0.01

xCT. The

maximum value is limited to 1200 A. Figure 22
illustrates the time-current curve for ground-fault
pickup.

Figure 21. Trip Unit display for ground-fault pickup.

SS

S

Seee

en

n

n

nsssso

o

o

orrrr,,,, A

A

A

A

SS

S

Seee

etttt P

P

P

Po

o

o

oiiiin

n

n

nttttssss

150–2000

0.20–0.60

2500–3200

0.20–0.37

4000

0.20–0.30

Table 14. Ground-fault pickup settings, as a function of sensor

rating.