GE Industrial Solutions EntelliGuard G Undervoltage Release User Manual
Entelliguard, G circuit breaker, Accessories
Introduction 
Undervoltage Release: 
 A device designed to open the breaker contacts 
and to prevent the breaker from closing when in 
a ‘No volt’ condition. On a de-energization the 
Undervoltage release activates the circuit breaker 
mechanism and ensures a rapid disconnection of 
the main contacts and the device prevents the 
Power Circuit Breaker from closing. The 
EntelliGuard G™ Undervoltage release is 
designed to react within a pre-defined Voltage 
band, only reacting when the voltage supply 
drops below the limits of this band. To prevent 
nuisance tripping due to short power 
interruptions or ‘Brown Outs’ the device has a 
built in delay of 50 Milliseconds when Voltage is at 
or below 50% of rated Voltage. Two under 
voltage Releases can be mounted in each Power 
Circuit Breaker. 
Table 1. 
 
Catalog No DC Voltage AC Voltage
GUVT024DR
24V
GUVT030DR
30V
GUVT048R
48V
48V
GUVT060DR
60-72V
GUVT120R
110-130V
120-130V
GUVT208AR
208V
GUVT240R
220-240V
220-240V
GUVT277R
250V
250-277V
 
 
 
 
 
DEH-41410 Installation Instructions
EntelliGuard
®
G Circuit Breaker
Accessories 
 
Undervoltage Release
 
 
WARNING: Before installing any accessories, turn the 
breaker OFF, disconnect it from all voltage sources, 
and discharge the closing spings.
 
 
 
 
 
For an External Time Delay Module (1-3 second 
delay) refer to Pub DEH-41406 
 
Inrush Power: 350VA
Steady state : 40VA
Use the following procedure to install the
Undervoltage Device accessory into the circuit 
breaker. 
 
1. Verify that the rating on the Undervoltage 
Device identification plate matches the voltage 
rating required for the application, as listed in 
Table 1. 
 
 
2. Turn the breaker off and discharge the closing 
springs by depressing the OFF and ON buttons in 
the sequence OFF-ON-OFF. Verify that the 
breaker OFF-ON indicator shows OFF on a green 
background and that the charge indicator shows 
DISCHARGE on a white background. If installing 
in a draw-out type breaker remove breaker from 
adaptor (cassette) before continuing. 
AVERTISSEMENT: Avant d’installer tout accessoire, 
mettre le disjoncteur en position OFF, le déconnecter 
de toute tension d’alimentation , et décharger les
resorts d’armement
 
3. Loosen the 6 screws on front cover (fascia) 
using a posidrive screw driver as shown in Fig 1.B 
Rotate the charging handle down and slide the 
front cover over the handle to remove the front 
cover as shown in Fig. 1.C. 
1