background image

64

Entellisys Low Voltage Switchgear

Appendix A. Torque Values

Table A-1—Torque Values for Low- voltage Equipment

Electrical Joint Hardware other than Cable Terminals

(Copper, Tin or Silver Plated)

Hardware

Size

Torque*

(ft/lbs)

Standard Nut with

Conical Spring Washer

or Lock washer

¼-20

3/8-16

½-13

5/8-11

7-10

25-30
35-40
45-55

*These torque values are for non-lubricated threads

Caution should be exercised when installing parts or

components to the compartment molded base. Torque 1/4-

inch screws slowly and do not exceed nine ft/lbs.
















Table A-2—Torque Values for Self-threading Screws in

Plastic

Wire

Size

Torque*

(in/lbs)

6
5
4
3

100

3
2
1

125

0
00

150

000
0000
200,000

200

250,000
300,000
350,000
400,000

250

500,000
600,000
700,000
750,000

300

800,000
900,000

1,000,000

400

1,250,000
1,500,000
1,750,000
2,000,000

500

*These torque values are for non-lubricated threads.