Adding signals using drag-and-drop, Editing properties, Channel configuration dialog box – GE Industrial Solutions Control System Toolbox For Configuring the Trend Recorder User Manual

Page 21

Advertising
background image

GEH-6408A Trend Recorder

Chapter 3 Types of Trends

13

Adding Signals Using Drag-and-Drop

À

To add a signal

The drag-and-drop feature
allows you to trend
automatically named signals
from Innovation Series
controllers and drives.

1.

From the

Block Area/Summary View

(or

Detached Summary View

),

click on a pin or a signal name in a block diagram.

2.

Drag the signal (using the mouse) to the top view of the Trend Window and
drop (release the mouse button). The

Trend Recorder Channel

Configuration

dialog box displays.

When a signal is added to the Trend Recorder from a controller, the toolbox checks
to see if the signal is an internal signal or an external DLAN+ signal. If it is an
internal signal, token (address) information should exist in the device for the signal.
This information is used to trend the signal.

If the signal is an external (DLAN+) signal, the toolbox attempts to find the signal in
the SDB. If it finds the signal, it determines if the signal is available on the DLAN+
that the device is attached to. Then, the signal can be trended.

Note

When a signal cannot be added or trending cannot be performed, an

appropriate error message displays. Follow the instructions from the message box to
correct the situation.

Once the signal is added to the trend, the range (upper and lower limits of Y-axis)
and other properties related to the signal can be set in several ways (see the next
section, Editing Properties).

Editing Properties

À

To set the signal range and other properties

Click on the signal in the
lower Signal View with the
right mouse and choose
Properties.

1.

From the

lower

Signal View

, click on the desired signal.

2.

From the

Edit

menu, choose

Edit Selected Signal

. Or, double-click on the

desired signal from the lower Signal View. The

Trend Recorder Channel

Configuration

dialog box displays.

Channel Configuration Dialog Box

Sets the upper
and lower limits of
the Y-axis labels
for the signal(s).

Allows you to
change the color,
line style, and line
thickness of the
pen used to
outline the trace
for the signal. A
trace is a visible
indication of the
path of a signal.

Click to display the Signal Scaling dialog box to
provide scaling for either an internal signal in a drive
or an external DLAN+ signal in a controller.
(See the next dialog box,

Signal Scaling.)

Note

If the line width is greater than one, only solid style is available.

Advertising