Alarms and events description and system troubleshooting guide

269

A

Breaker Close Command
Rejected Breaker Locked Out

Breaker is locked out, so CPU has rejected
the close command

If breaker has a manual lockout, verify
that the lockout has been reset.

If the breaker has a network interlock, the
control logic is likely causing the breaker
to reject the close command.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Attention IO Card Detection
Mismatch Found 0 of 1

CPU expected 1 discrete I/O card, but
detected none

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 0 of 2

CPU expected 2 discrete I/O cards, but
detected none

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 1 of 0

CPU expected no discrete I/O cards, but
detected 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 1 of 2

CPU expected 2 discrete I/O cards, but
detected 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 2 of 0

CPU expected no discrete I/O cards, but
detected 2

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention IO Card Detection
Mismatch Found 2 of 1

CPU expected 1 discrete I/O card, but
detected 2

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-2 Sequence of events description and troubleshooting guide

Event

Description

Notes and Troubleshooting tips