GE Industrial Solutions EntelliGuard G Command Closing Coil User Manual
Accessories entelliguard, G circuit breaker, Command closing coil
Introduction 
Command Closing Coil: 
Command Close coil is used to switch ON the 
Power Circuit Breaker remotely. When energized, 
it releases the spring charged mechanism thus 
ensuring a rapid connection of the main contacts. 
The Command Close coil offers an extended 
functionality in addition to all the features of the 
standard closing coil. Additional connections 
allow it to be wired out through the trip unit and 
can be accessed electrically through the 
communications bus. It also has an extra round 
‘ON’ push button that fits onto the breaker front 
fascia, which can be locally operated manually to 
close the breaker. 
 
Table 1. Catalog Numbers and Ratings
Catalog No
DC Voltage
AC Voltage
GCCC024DR
24V
GCCC030DR
30V
GCCC048R
48V
48V
GCCC060DR
60-72V
GCCC120R
110-130V 110-130V
GCCC208AR
208V
GCCC240R
220-240V 220-240V
GCCC277R*
250V
250-277V
*Electrical close switch push button cannot be
used with GCCC277R
 
 
 
DEH-41418 Installation Instructions
 
 
Accessories
EntelliGuard
®
G Circuit Breaker
Command Closing Coil
 
 
 
 
 
WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,
and discharge the closing spings.
 
 
 
 
 
Inrush Power: 350VA
Steady state : 50VA
 
Use the following procedure to install the 
Command Closing Coil accessory into the circuit 
breaker. 
 
1. Verify that the rating on the Command Closing 
Coil identification plate matches the voltage 
rating required for the application, as listed in 
Table 1. 
 
 
2. Turn the breaker off and discharge the closing 
springs by depressing the OFF and ON buttons in 
the sequence OFF-ON-OFF. Verify that the 
breaker OFF-ON indicator shows OFF on a green 
background and that the charge indicator shows 
DISCHARGE on a white background. If installing 
in a draw-out type breaker remove breaker from 
adaptor (cassette) before continuing. 
AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation , et décharger les
resorts d’armement
 
3. Loosen the 6 screws on front cover (fascia) 
using a posidrive screw driver as shown in Fig 1.B 
Rotate the charging handle down and slide the 
front cover over the handle to remove the front 
cover as shown in Fig. 1.C. 
 
 
 
1