GE Industrial Solutions 300_400 Line NEMA size 0 & 1 User Manual
Combination magnetic starters, Instructions for nema size 0 & 1, Geh-5193 instruction
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Max.Hp
For AC Motors
Starter
Max
Current
Rating
Contactor
Max.
Current
Rating
AC
Volts
Single-
Phase
Poly-
Phase
Size 0
115
1
-
200
-
3
230
2
3
18 amp
(open
and
enclosed)
20 amp
(open)
18amp
(enclosed)
460—575
-
5
Size 1
115
2
-
200
-
7½
230
3
7½
27 amp
(open
and
enclosed)
30 amp
(open)
27amp
(enclosed)
460—575
-
10
Note: For starters with one or more 
normally closed contacts, perform steps 
1 and 2 shown under Coil Replacement. 
Withdraw spring clip (B—Figure 1) and 
remove armature, coil, and magnet from 
device. Remove return spring from center 
of movable arm. Remove molded cover 
and stationary contacts before lifting 
movable arm from device. 
 Normally Closed Contacts 
 The contacts may be converted from 
normally open to normally closed with no 
additional parts. Perform steps 1 through 
4 shown under Coil Replacement. Lift coil 
and magnet from movable arm. Remove 
return spring from center of movable 
arm. Depress movable contact spring 
and spring seat against movable contact 
and rotate these parts 1/2 turn without 
removing them from window. Remove 
the stationary contacts. Install the 
movable arm in the device. Install the 
stationary contacts so that their silver 
pads face the movable contact silver 
pads. Reassemble the device. To change 
contacts from normally closed to 
normally open position, reverse the 
above procedure. 
 Check For Welded Contacts In 
Overload Relay  
With power disconnected, disconnect 
the control wiring from the relay 
terminals. Place a bell set or resistance 
measuring instrument across relay 
terminals. Depress and release reset 
arm to insure relay is reset
.
6. Remove screws holding stationary 
contacts in place and remove stationary 
contacts. 
7. Reassemble device by reversing 
procedure. 
 
Combination 
Magnetic Starters
CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408 
CR410-CR415, CR487, CR490, CR492, CR494 Series
Motor branch circuit and control circuit 
over- current protection should be 
supplied in accordance with the 
National 
Electrical
Code.
CR305
contactors are suitable for use on a 
circuit capable of delivering not more 
than 5,000 RMS symmetrical amperes, 
600 volts maximum when protected by 
H, J, K1, K5, RK1, RK5 class fuses, or a 
circuit breaker having an interrupting 
rating not less than 5,000 RMS 
symmetrical amperes. 
Installation
Before connecting controller to power 
supply: 
1. Remove all packing. 
2. Clean magnet mating surfaces of any 
dirt or foreign matter. 
3. Select and install heaters in accordance 
with heater table. 
4. Operate movable magnet and operating 
arm by pressing on the nameplate to 
assure free movement. 
5. Mount on a sturdy vertical support. 
6. Make the electrical connections. 
7. The starter overload relay may be reset 
manually by depressing and releasing the 
reset arm.
Coil Replacement 
1. Remove power from device. 
2. Press against coil while pulling up 
slightly on coil retainers (A—Figure 1) and 
move retainers away from coil. 
3. Withdraw magnet assembly, coil, 
molded cover, and movable arm from 
device. 
4. Withdraw spring clip (B—Figure 1) and 
remove armature from movable arm. 
5. Remove coil from magnet. 
6. Replace coil. 
7. Reassemble device by reversing 
procedure. 
Contact Replacement
1. Perform steps 1 through 5 under 
Coil Replacement. 
2. Remove magnet from molded cover 
and movable arm. 
3. Remove return spring from center 
of movable arm. 
4. Remove molded cover from 
movable arm. 
5. Depress and slide movable contact 
and spring from movable arm. 
Instructions For 
NEMA size 0 & 1 
Supersedes GEH-4793B 
& GEH4796B
GEH-5193 Instruction
CAUTION:
Before installing in a nuclear
application, determine that the product is 
intended for such use. 
WARNING:
Disconnect power
before Installing or servicing.
Description
General Electric 300/400-Line full-voltage 
motor starters include a magnetic 
contactor and a three-leg block overload 
relay, providing motor protection against 
running and stalled motor overloads. The 
overload relay is provided with a yellow 
trip indicator located to the right of the 
reset arm, and is visible when the 
overload relay is tripped
.
Ratings—600 V Maximum
Figure1.Typical 300/400-Line magnetic starter
Figure2