1.1.13 Connecting to Mains and Motor

The frequency converter is designed to operate all standard three-phased asynchronous motors.

The frequency converter is designed to accept mains/motor cables with a maximum cross-section of 4 mm

2

/10 AWG (M1, M2 and M3) and maximum cross-

section 16 mm

2

/6 AWG (M4 and M5).

•

Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor
metal.

•

Keep motor cable as short as possible to reduce the noise level and leakage currents.

•

For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY.

•

Also see EMC-Correct Installation in Operating Instruction MG.02.AX.YY.

Step 1: First, mount the earth wires to earth terminal.

Step 2: Connect motor to terminals U, V and W.

Step 3: Mount mains supply to terminals L1/L, L2 and
L3/N (3-phase) or L1/L and L3/N (single-phase) and tighten.

Illustration 1.2: Mounting of earth cable, mains and motor wires.