Module – GE Industrial Solutions 12V Mega TLynx User Manual
Page 14
Data Sheet 
May 4, 2012
12V Mega TLynx
TM
: Non-Isolated DC-DC Power Modules:
6.0 – 14Vdc Input; 0.8Vdc to 3.63Vdc Output; 30A output
current
LINEAGE
POWER
14
Good layout techniques should be observed when 
using multiple units in parallel. To implement forced 
load sharing, the following connections should be 
made: 
• The share pins of all units in parallel must be
connected together. The path of these 
connections should be as direct as possible. 
• All remote-sense pins should be connected to
the power bus at the same point, i.e., connect 
all the SENSE
(+)
pins to the
(+)
side of the bus.
Close proximity and directness are necessary 
for good noise immunity 
Some special considerations apply for design of 
converters in parallel operation: 
• When sizing the number of modules required 
for parallel operation, take note of the fact that 
current sharing has some tolerance. In 
addition, under transient condtions such as a 
dynamic load change and during startup, all 
converter output currents will not be equal. To 
allow for such variation and avoid the likelihood 
of a converter shutting off due to a current 
overload, the total capacity of the paralleled 
system should be no more than 75% of the 
sum of the individual converters. As an 
example, for a system of four 12V Mega 
TLynx
TM
converters in parallel, the total current
drawn should be less that 75% of (4 x 30A) , 
i.e. less than 90A. 
• All modules should be turned on and off
together. This is so that all modules come up at 
the same time avoiding the problem of one 
converter sourcing current into the other 
leading to an overcurrent trip condition. To 
ensure that all modules come up 
simultaneously, the on/off pins of all paralleled 
converters should be tied together and the 
converters enabled and disabled using the 
on/off pin. 
• The share bus is not designed for redundant
operation and the system will be non-functional 
upon failure of one of the unit when multiple 
units are in parallel. In particular, if one of the 
converters shuts down during operation, the 
other converters may also shut down due to 
their outputs hitting current limit. In such a 
situation, unless a coordinated restart is 
ensured, the system may never properly restart 
since different converters will try to restart at 
different times causing an overload condition 
and subsequent shutdown. This situation can 
be avoided by having an external output 
voltage monitor circuit that detects a shutdown 
condition and forces all converters to shut 
down and restart together. 
When not using the active load sharing feature, 
share pins should be left unconnected. 
Tunable Loop
TM
The 12V Mega TLynx
TM
modules have a new
feature that optimizes transient response of the 
module called Tunable Loop
TM
.
 
External capacitors are usually added to the output 
of the module for two reasons: to reduce output 
ripple and noise (see Fig. 29) and to reduce output 
voltage deviations from the steady-state value in the 
presence of dynamic load current changes. Adding 
external capacitance however affects the voltage 
control loop of the module, typically causing the 
loop to slow down with sluggish response. Larger 
values of external capacitance could also cause the 
module to become unstable. 
The Tunable Loop
TM
allows the user to externally
adjust the voltage control loop to match the filter 
network connected to the output of the module. The 
Tunable Loop
TM
is implemented by connecting a
series R-C between the SENSE and TRIM pins of 
the module, as shown in Fig. 34. This R-C allows 
the user to externally adjust the voltage loop 
feedback compensation of the module. 
 
MODULE
VOUT
SENSE
TRIM
GND
RTUNE
CTUNE
RTrim
C O
Figure. 34. Circuit diagram showing connection 
of R
TUME
and C
TUNE
to tune the control loop of
the module. 
 
Recommended values of R
TUNE
and C
TUNE
for
different output capacitor combinations are given in 
Tables 2 and 3. Table 2 shows the recommended 
values of R
TUNE
and C
TUNE
for different values of
ceramic output capacitors up to 1000uF that might 
be needed for an application to meet output ripple 
and noise requirements. Selecting R
TUNE
and C
TUNE
according to Table 2 will ensure stable operation of 
the module. 
 
In applications with tight output voltage limits in the 
presence of dynamic current loading, additional