Figure C







4 Inspect the arc plates and sides of the

moldings for signs of wear or damage
and replace if necessary.

5 Install the arc chamber assembly by

tightening the mounting screws to
torque of 8-10 Nm (5.9 – 7.4 ft-lbs)

6 Slide in the slider back to original

position